1. Israel
  2. All 3M Products
  3. Electrical
  4. Splices & Accessories
  5. Resin Joints & Splices
  6. 3M™ Scotchcast™ Flexible Splice 82-F1 (2131)

3M™ Scotchcast™ Flexible Splice 82-F1 (2131)

  • 3M ID 80611468358
  • UPC 051128591765

The self-curing resin forms a splice or repair that resists abrasion

Designed to splice or re-jacket non-shielded portable power cable and portable cord

Suitable for use with compression inline connectors

View more details

Details

Highlights
  • The self-curing resin forms a splice or repair that resists abrasion
  • Designed to splice or re-jacket non-shielded portable power cable and portable cord
  • Suitable for use with compression inline connectors
  • 1 kV-rated for multi-conductor and 5 kV-rated for single-conductor cable applications
  • MSHA Approved and RoHS 2011/65/EU Compliant

3M™ 82-F Series Resin Compression Inline Cable Splice Kit with flame-retardant compound 2131, is designed for inline splicing on non-shielded portable power cables and cords. The wet/dry flexible power cable splice kit is suitable for use on single- and multi-conductor cables, depending on the voltage rating

3M™ 82 F Series Resin Inline Cable Splice Kit includes Scotch® rubber splicing tape 23, Scotchcast™ compound 2131 and Three M Ite™ Elek Tro Cut™ abrasive cloth 80J grit. The semi flexible compound offers permanent splicing to bend with the cable for easy installation, reeling and handling. The smooth, tapered splice prevents cable hang ups and splice end lifting. The flame retardant compound 2131 is a self curing resin that bonds to itself and modern cable jackets. This kit is perfect for splicing 1 kV rated multiple conductors and 5 kV rated single conductors. RoHS 2011/65/EU Compliant and MSHA Approved.

Typical Properties

Related Products

Brands Scotchcast™
Cable Type multi core, non shielded, rubber insulated reeling cables
Conductor Amount Single, Multiple
Connection Max Outside Diameter Single Conductor - 0.62 inch, Multiple Conductors - 0.90 inch
Dielectric Strength (V/mil) 343 V/mil
Flame Retardant Resin only
Gel Time 17 min 73 °F (23 °C)
Hardness 82 Shore A
Indoor/Outdoor Both
Insulation Outside Diameter Range (metric) 6.0 - 20.0 mm
Maximum Conductor Size 50 mm²
Maximum Insulation Outside Diameter 20 Millimetre
Maximum Voltage 5 Kilovolt
Minimum Conductor Size 6 mm², 14 mm²
Minimum Insulation Outer Diameter (Metric) 6 Millimeter
Mining Sector Approval Yes
Model Cast Resin
Number of Conductors 3 , 4
Product Series 82-B Series
Resin Type SC 2131
20 of 27